Thermostatic Expansion Valve - Sporlan - Type C | Parker NA

Thermostatic Expansion Valve - Sporlan - Type C | Product Series

Filter by

    No filters selected

Get your Parker account Today!

Create one account to manage everything you do with Parker, from your shopping preferences to your application access.

Thermostatic Expansion Valve - Sporlan - Type C

Thermostatic Expansion Valve - Sporlan - Type C

Sporlan Type C TEV's are designed for use on Air Conditioning and Refrigeration units. They regulate refrigerant flow by maintaining a nearly constant superheat at the evaporator outlet. The S and R series valves serve as functional replacements.

Technical Specifications

  • Application: Ultra Low Temp Refrigeration, Low Temp Refrigeration, Commercial Refrigeration, Air Conditioning, De- Super Heating Charge
  • Product Type: C-Valve
  • Refrigerant Type: R-22, R-407C, R-407A, R-134A, R-12, R-401A, R-409A, R-404A, R-502, R-408A, R-507, R-402A
  • Thermostatic Charge: GP35, GP, ZP, Z, C, CP60, ZPM, CP65, L2, CP100, GA, X, L1, CP115, ZP40, CP85, GP15
  • Nominal Capacity: 2 to 8 ton
  • Inlet Connection Size: 1/2 to 3/8 inch SAE
  • Outlet Connection Size: 1/2 to 5/8 inch (SAE)
  • Maximum Operating Pressure: 31 bar, 450 psi
  • Equalizer Connection Type: Externally Equalized, Internally Equalized
  • Capillary Tube Length: 1.524 m, 3.048 m, 6.096 m, 5 ft, 10 ft, 20 ft
  • Strainer Type: 80 Mesh Removable
  • Filter Element Type: 83
Safety Warning

Full Product Description

The Sporlan Type C thermostatic expansion valves have a brass bar stock body. The C valve has SAE connections. It is available with adjustable superheat, long lasting replaceable power element and accessible internal parts. Each valve is factory tested to ensure positive leak-free performance.

Historical Markets:
• Air Conditioning
• Refrigeration
• Transportation
• Industrial Refrigeration
• Ultra Low Temp Applications

Features and Benefits:
• Permanent Inlet strainer
• Thermostatic charges available to match system conditions
• Available with internal equalizer or external equalizer
• Design working pressure for the C valves is 450 psi (31 bar)

Applications:
• Heat Pumps
• Air Conditioning – Residential, Commercial, Chillers
• Refrigeration – Cases, Coolers, Walk in Coolers, Freezers
• Capacity ranges from 2 to 10 tons R-22
• Transportation

For over 80 years the Sporlan Division of Parker Hannifin has set the industry standard for the development and manufacture of leading edge HVACR components. Our outside technical sales force and application engineering team focuses on refrigeration system applications and troubleshooting for service technicians, distribution channel partners, and original equipment manufacturers.