Solenoid 3-Way Heat Reclaim Valve | Série de produits

Filtrer par

    Aucun filtre slectionn

Créez votre compte Parker aujourd'hui !

Créez un compte pour gérer tout ce que vous faites avec Parker, de vos préférences shopping à votre accès aux applications.


LOADING IMAGES
Solenoid 3-Way Heat Reclaim Valve Solenoid 3-Way Heat Reclaim Valve

Solenoid 3-Way Heat Reclaim Valve

Parker Type 3 Way series valves primary purpose is to control automatically the flow of fluids, liquid or gas. Parker 3 Way Valves may be applied to divert flow of refrigerant in heat reclaim, reheat, or defrost applications.

Caractéristiques techniques

  • Type de produit : 3-Way Split Condenser Valve
  • Type de raccordement : ODF Sweat
  • Taille de l'orifice : 3/4 inch, 1-1/4 inch
  • Pression de service maximale : 400 psi, 680 psi
  • Tension d'entrée : 24 VAC 50/60Hz, 120 VAC 50/60Hz, 208 to 240 VAC 50/60Hz, 120-208-240 VAC 50/60Hz (available at additional charge)
  • Consommation électrique : 10 W
  • Type de bobine : PKC-1
  • Options supplémentaires : Conduit Boss (No Additional Charge) or Junction Box (No Additional Charge)
Safety Warning

Description complète du produit

The Parker 3 Way heat reclaim valves primary purpose is to control automatically the flow of fluids, liquid or gas. When the coil is de-energized the valve diverts refrigerant to the normal condenser. When the coil id energized the valve diverts refrigerant to the reclaim condenser. The 8D and 12D valves are powder coated steel bodies with extended copper connections. For air conditioning or refrigeration applications it is important to use system capacity, refrigerant, type of fluid, temperature and pressures. It is not recommended to size by line size. Refer to literature or selection program for capacity data and details. Each valve is factory tested to ensure positive leak-free performance.

Markets:

• Air Conditioning
• Refrigeration
• Industrial Refrigeration
• Transportation

Features/Benefits:

• Class F coils
• 3 Way pilot eliminates costly low side leaks
• “B” type reduces install cost by eliminating the need for a solenoid valve on systems requiring idle condenser pump out.
• Mount in vertical or horizontal lines
• Synthetic seating material for tight closing
• Synthetic coated metal gaskets minimize external leaks
• Maximum working pressure for the (S)B5D series valves is 650 psi (45 bar), For the (S)8D, (S)12D, and (S)16D it is 450 psi (31 bar) and (S)8D-HP and (S)12D-HP it is 680 psi (47 bar)

Applications:

• Air Conditioning – Residential, Heat pumps, Chillers, Commercial units, Industrial
• Refrigeration – Freezers, Walkin units, Racks
• Industrial Refrigeration
• Transportation – Truck/Trailer, Containers

Documents annexes

×
Produits

687PDC
687382